CPX-4AE-T (541486) analogue module

Číslo výrobku:

OT-FESTO023524

456,91 € vč. DPH
ks
vlastnosti
Di­mensi­ons W x L x H 50 mm x 107 mm x 50 mm,
(Incl. lin­king block and con­nec­tors)
Di­a­gno­sis Pa­ra­me­t­rier­fehler,
Draht­bruch pro Kanal,
Gren­zwert­ver­le­t­zung pro Kanal,
Kurz­schluss Ein­gan­gs­sig­nal
Pa­ra­me­te­ri­sing For­cen pro Kanal,
Gren­zwertüberwa­chung/Kanal,
Maßeinheit,
Messwertglättung,
Sen­sor­typ pro Kanal,
Überwa­chung Draht­bruch/Kanal
LED dis­plays 1 Sa­m­mel­di­a­gnose,
4 Ka­nal­di­a­gnose
In­ter­nal cycle time 250 ms
Ope­ra­ting vol­tage range DC [V] 18 to 30
In­trin­sic power input at ope­ra­ting vol­tage Type 50 mA
No­mi­nal ope­ra­ting vol­tage DC [V] 24
Po­ten­tial se­pa­ration chan­nel - in­ter­nal bus yes
Po­ten­tial se­pa­ration chan­nel - chan­nel no
Corro­sion re­sistant class KBK (In in­te­gra­ted con­di­tion),
1 - low corro­sion stress
Bea­ring tem­pe­ra­ture [°C] -20 to 70
Pro­tection ca­te­gory De­pends on con­nection block
am­bi­ent tem­pe­ra­ture [°C] -5 to 50
Pro­duct wei­ght [g] 47,0
Max. line len­gth 200 m,
Shiel­ded
Housing ma­te­rial PC,
PA re­in­for­ced
Quan­tity in­puts 4
Fuse (short ci­r­cuit) In­ter­nal electro­nic fuse
Re­pe­a­ta­bi­lity 0.05 % at 25 °C
Use error li­mits re­la­ted to am­bi­ent tem­pe­ra­ture range ±0,6 %
Base error limit at 25 °C ±0,6 K für Pt-​Sensoren
Data for­mat 15 bit + Sign,
Bi­nary dis­play in ten­ths of de­grees
Sen­sor type Ni 100,
Ni 1000,
Ni 120,
Ni 500,
Pt 100,
Pt 1000,
Pt 200,
Pt 500
Další informace k OT-FESTO023524
hmotnost 47,0 g / ks
GTIN 4052568179663
Celní číslo zboží 85389099
výrobce Festo
Dokumenty

 
Všechny údaje se rozumějí jako nezávazné směrné hodnoty! Za výběr údajů nepotvrzených písemně nepřebíráme žádnou záruku. Údaje o tlaku se vztahují, pokud není uvedeno jinak, ke kapalinám skupiny II při +20°C.