Item group

Refrigeration dryer - high efficiency, KAESER TA/TB/TC

Description:

Highly efficient Kaeser refrigeration dryer with energy-saving SEROTEC Control. In 1-shift operation, up to 88% of the electricity requirement can be saved compared to a conventional refrigeration dryer with hot gas bypass control. High-quality equipment with corrosion-free condensate trap and electronically controlled Eco-Drain condensate drain (type TA 5: Float valve).

Pressure dew point:

+3°C

Operating pressure:

3 - 16 bar

Ambient temperature:

+3 °C to +43 °C

Inlet temperature compressed air:

max. +55 °C

Refrigerant:

R-513a

Condensate drain:

Electronic condensate drain (type TA 5: Float valve), G 1/4" (IT)

Operating voltage:

230V AC (alternating current)

Calculation of volume flow at non-reference conditions:

Volume flow = Volume flow at reference conditions x Kp x Kte x Ktu

Correction factor input pressure (Kp):

3 bar: Kp=0,75 - 4 bar: Kp=0,84 - 5 bar: Kp=0,90 - 6 bar: Kp=0,95 - 7 bar: Kp=1,00 - 8 bar: Kp=1,04 - 9 bar: Kp=1,07 - 10 bar: Kp=1,10 - 11 bar: Kp=1,12 - 12 bar: Kp=1,15 - 13 bar: Kp=1,17 - 14 bar: Kp=1,19 - 15 bar: Kp=1,21 - 16 bar: Kp=1,23

Correction factor compressed air inlet temperature (Kte):

+30°C: Kte=1,20 - +35°C: Kte=1,00 - +40°C: Kte=0,83 - +45°C: Kte=0,72 - +50°C: Kte=0,60 - +55°C: Kte=0,49

Ambient temperature correction factor (Ktu):

+25°C: Ktu=1,00 - +30°C: Ktu=0,99 - +35°C: Ktu=0,97 - +40°C: Ktu=0,94 - +43°C: Ktu=0,92
*Performance data at reference conditions ISO 7183, option A: Operating pressure 7 bar, ambient temperature +25 °C, compressed air inlet temperature +35 °C.

Documents:

More information Less information
Refrigeration dryer - high efficiency, KAESER TA/TB/TC:
7 of 7 articles
€2,265.76 incl. VAT
Immediately available
€2,595.39 incl. VAT
Immediately available
€3,167.78 incl. VAT
Immediately available
€4,076.94 incl. VAT
Immediately available
€5,107.48 incl. VAT
Immediately available
€6,171.34 incl. VAT
Immediately available
€6,846.07 incl. VAT
Immediately available
All data are to be understood as non-binding reference values! We do not assume liability for any data selection not confirmed in writing. Unless otherwise specified, pressure values refer to liquids from Group II at +20°C.
Payment options:

Cash on delivery

Invoice